| Alarm Valves | |
| Exterior | Quarterly |
| Interior | 5 Years |
| Strainers, filters, orifices | 5 Years |
| Backflow Prevention Assemblies | |
| Reduced pressure | Weekly |
| Reduced-pressure detectors | Weekly |
| Interior | 5 years |
| Check Valves | |
| Interior | 5 Years |
| Control Valves | |
| All valves except locked or supervised | Weekly |
| Locked or supervised | Monthly |
| Electronically supervised | Quarterly |
| Dry pipe valves/quick-opening devices | |
| Enclosure (during cold weather) | - |
| Exterior | Monthly |
| Interior | Annually |
| Strainers, filters, orifices | 5 Years |
| Deluge Valves | |
| Enclosure (during cold weather) | Daily/weekly |
| Exterior | Monthly |
| Interior | Annually/ 5 years |
| Strainers, filters, orifices | 5 Years |
| Fire Department connections | Quarterly |
| Gauges | Quarterly |
| Hose valves | Quarterly |
| Preaction valves | |
| Enclosure (during cold weather) | - |
| Exterior | Monthly |
| Interior | Annually/ 5 years |
| Strainers, filters, orifices | 5 Years |
| Pressure-regulating and relief valves | |
| Master pressure regulating | Weekly |
| Sprinkler system pressure reducing | Quarterly |
| Hose connection pressuer regulating | Annually |
| Fire pump circulation relief | With no flow test |
| Fire pump main pressure-relief | With fire pump test |
| Valve supervisory signal initiating device | Quarterly |
| Supervisory signal devices (except valve supervisory switches) | Quarterly |
| Air compressors and nitrogen generators | Monthly |
| Waterflow Alarms | Quarterly |